Transformer Sizing Calculator

Transformer Sizing Calculator

This calculator helps determine the appropriate transformer size and protection based on connected loads and NEC 450.3 requirements.

Equipment
Transformer
Results

Connected Equipment

Equipment kW Real Power PF Power Factor Qty DF Diversity Factor kVA =kW/(PF×Qty×DF)
Total Load (kVA):
Diversity Factor:
Total DF Load (kVA): = Total kVA × DF
Future Growth (%):
Required Transformer Size (kVA): = DF Load × (1 + Growth%)

Transformer Details

Primary Voltage (L-L, V):
Secondary Voltage (L-L, V):
Connection Type:
Transformer Impedance (%Z):
Efficiency at Full Load (%):
Efficiency at 1/4 Load (%):
Selected Transformer Size (kVA):
Protection Type:
Protection Method:

Calculation Results

Voltages

Primary Line Voltage (L-L): VL-L = Vinput V
Primary Phase Voltage (L-N): VL-N = VL-L/√3 (Y) or VL-L (Δ) V
Secondary Line Voltage (L-L): VL-L = Vinput V
Secondary Phase Voltage (L-N): VL-N = VL-L/√3 (Y) or VL-L (Δ) V

Currents

Primary Line Current: IL = kVA×1000/(√3×VL-L) A
Primary Phase Current: Iφ = IL (Y) or IL/√3 (Δ) A
Secondary Line Current: IL = kVA×1000/(√3×VL-L) A
Secondary Phase Current: Iφ = IL (Y) or IL/√3 (Δ) A

Transformer Losses

Copper Loss @ Full Load: Pcu = (16/15)×(LossFL-LossQL)×1000 W
Core Loss: Pcore = LossFL×1000 - Pcu W
Total Losses @ Full Load: Ptotal = Pcu + Pcore W
Total Losses @ 1/4 Load: Ptotal = (Pcu/16) + Pcore W

Protection Sizing (NEC 450.3)

Primary Protection Size: Iprot = IL×1.25 (primary only) or ×2.5 (both) A
Secondary Protection Size: Iprot = IL×1.25 A

Transformer Educational Content

Transformer Fundamentals

Transformers are electrical devices that transfer energy between circuits through electromagnetic induction. They are essential for:

  • Voltage step-up/down for efficient power transmission
  • Isolation between circuits
  • Impedance matching
Turns Ratio: V₁/V₂ = N₁/N₂
Current Ratio: I₁/I₂ = N₂/N₁
Impedance Ratio: Z₁/Z₂ = (N₁/N₂)²

Transformer Types

TypeDescriptionCommon Applications
Power TransformerLarge, high efficiencyUtility substations
Distribution TransformerMedium sizeCommercial buildings
Isolation Transformer1:1 ratioEquipment protection
AutotransformerSingle windingVoltage adjustment

Connection Types

ConnectionPrimary VoltageSecondary VoltageCharacteristics
Y-YLine-to-lineLine-to-lineNeutral available, 3-wire or 4-wire
Δ-ΔPhasePhaseNo neutral, good for unbalanced loads
Y-ΔLine-to-linePhaseStep-down, no secondary neutral
Δ-YPhaseLine-to-lineStep-up, neutral available

Transformer Losses

Transformers have two main types of losses:

  1. Copper Losses (I²R): Vary with load current (proportional to square of load)
  2. Core Losses (Iron Losses): Constant regardless of load (hysteresis and eddy currents)
Efficiency: η = (Output Power) / (Output Power + Losses) × 100%

Typical Efficiency Values:

Transformer SizeFull Load Efficiency1/4 Load Efficiency
15kVA98-98.5%97-97.5%
75kVA98.5-99%97.5-98%
300kVA99-99.3%98-98.5%

NEC 450.3 Protection Rules

Protection TypePrimary ProtectionSecondary Protection
Primary Only≤125% rated currentNot required
Primary + Secondary≤250% rated current≤125% rated current

Note: For transformers over 600V, different rules apply. This calculator covers common low-voltage applications.

Practical Example

Scenario:

Commercial building with 50kW lighting load at PF=0.95 and 30kW HVAC load at PF=0.85. Diversity factor=0.8, future growth=25%.

Calculation Steps:

Lighting kVA: 50kW / 0.95 = 52.63kVA
HVAC kVA: 30kW / 0.85 = 35.29kVA
Diversified Load: (52.63 + 35.29) × 0.8 = 70.34kVA
With Future Growth: 70.34 × 1.25 = 87.92kVA
Selected Size: Next standard size = 100kVA

Standard Transformer Sizes (kVA)

Single PhaseThree Phase
0.05, 0.1, 0.25, 0.53, 6, 9, 15
1, 1.5, 2, 3, 525, 30, 37.5, 45
7.5, 10, 15, 2550, 75, 100, 150
37.5, 50, 75, 100200, 250, 300, 500